  xmc0 series definite purpose contactors description hongfa ?s definite purpose contactor xmc0 meets the rigorous demands of the hvac, refrigeration, heating, data processing, welding, elevators, hoist & cranes, pool, commercial spa, and food service equipment industries. the contactor series meet and exceed the requirements for iec 60947-4-1, gb 14048.4, ul 508, ul 60947-4-1, and ul 1995. features 1. tools-free accessories for quick & easy snap on assembly. 2. various terminal options for specific application. 3. universal mounting plate. 4. heavy duty silver metal oxide contacts to provide long electrical endurance. 5. class f (155c) coil insulation systems with a broad range of 50/60hz voltage offerings. 6. protective coil cover option available for the 1 & 2 pole contactors. 7. ul(usr/cnr) and ccc approved, some models semko, keti or tv plus. environmental characteristics protective treatment total climate tropical use ?th? operating position vertical or horizontal (metal/plastic base mounting) operation -40c +70c/ -40 f +158 f ambient temperature storage -40 c +70c / -40 f +158 f relative humidity 90-95%rh at 40c pollution degree 3
0 -50 j33 .e b b c 0 0 f g z x blank = quad terminals in 1- and 2- pole models and dual terminals in 3-pole models g = none qc terminals q = quad terminals in 3-pole models (only the side no coil terminals) full load amperes (fla) c = slotted & hex head washer w/ quick connect d = box lug w/ quick connect e = box lug w/ quick connect (line side) slotted & hex head washer w/ quick connect (load side) f = slotted & hex head washer w/ quick connect (line side) box lug w/ quick connect (load side) 1 = 1-pole+shunt 2 = 2-pole 7 = 1-pole 3 = 3-pole 3a = 2-pole (3p frame) jmn = matching mechanically interlocked block (3p frame). "m" = 2 or 3, number of poles of the contactor a(on the left) and "n" = 2 or 3, number of poles of the contactor b(on the right). note: please contact us if you have any other request. coil voltage mounting plate b = metal plate blank = quantum series - serviceable /metal plate note: if "00" will be the final digits in selection, omit from model nomenclature. for example 34p = 1nc 0.250" quick connect terminal on left side 1no pressure plate screw on right side lr1 = 2 spdt on left side 1 spdt(position 1 of microswitch block) on right side 3r2 = 1nc 0.250" quick connect terminal on left side 1 spdt(position 2 of microswitch block) on right side customer assigned suffix "x" where "x" may be any alphanumeric character or any combined alphanumeric character. contact construction style (for 50/63 fla only) blank = flat construction in shape z = bend construction in shape(no "break all lines" restriction) power quick terminals note: please contact us if you have any other request. top cover power terminals b = short cover blank = quantum series - serviceable /short cover number of poles type model nomenclature - ordering information product type design sequence number 0 = design sequence number xmc = contactor series xmc 50 = 50a 63 = 63a 75 = 75a 90 = 90a 20 = 20a (same as 25a) 25 = 25a 32 = 32a 40 = 40a option e = 24vac 50/60hz f = 110-120vac 50/60hz i = 208-220vac 50hz 208-240vac 60hz l = 277vac 60hz n = 380-415vac 50hz 440-480vac 60hz u = 550-600vac 50/60hz notes: 1.quantum series only available for 3, 3a or jmn. 2.please contact us if you have any other request. coil terminals blank = dual qc without screw in 1- and 2- pole models and single qc with screw in 3-pole models f = dual qc in 3-pole models auxiliary contacts or microswitch on right side (for 3-pole only) 0 = none (standard type) 1 = 1nc + 1no, 0.250" quick connect terminal 3 = 1nc, 0.250" quick connect terminal 4 = 1no, 0.250" quick connect terminal 5 = 2nc, 0.250" quick connect terminal 6 = 2no, 0.250" quick connect terminal 1p = 1nc + 1no, pressure plate screw 3p = 1nc, pressure plate screw 4p = 1no, pressure plate screw 5p = 2nc, pressure plate screw 6p = 2no, pressure plate screw r = 2 spdt r1 = 1 spdt, left side(position 1) of microswitch block r2 = 1 spdt, right side(position 2) of microswitch block 0 = none (standard type) 1 = 1nc + 1no, 0.250" quick connect terminal 3 = 1nc, 0.250" quick connect terminal 4 = 1no, 0.250" quick connect terminal 5 = 2nc, 0.250" quick connect terminal 6 = 2no, 0.250" quick connect terminal 1p = 1nc + 1no, pressure plate screw 3p = 1nc, pressure plate screw 4p = 1no, pressure plate screw 5p = 2nc, pressure plate screw 6p = 2no, pressure plate screw l = 2 spdt l1 = 1 spdt, left side(position 1) of microswitch block l2 = 1 spdt, right side(position 2) of microswitch block auxiliary contacts or microswitch on left side (for 3-pole only)
a 11 p q x m 10 q x j 1q x 2 = match with 75-90a 1q = match with 25-63a(quantum series) basic designation basic designation c03 = for xmc0 3p series definite purpose contactors. used function blank = match with 3p contactor q = match with quantum series option microswitch at left side(position 1) for microswitch assembly microswitch at right side(position 2) for microswitch assembly interlock blocks: c03 auxiliary contact blocks: microswitch blocks: accessory category c03 = for xmc0 3p series definite purpose contactors. blank = 0.250" quick connect terminals p = pressure plate screw(none qc terminals) quick connect terminals 01 = 1nc 10 = 1no 11 = 1nc + 1no 02 = 2nc 20 = 2no note : nc = normally closed, no = normally opened. customer assigned suffix "x" where "x" may be any alphanumeric character or any combined alphanumeric character. customer assigned suffix "x" where "x" may be any alphanumeric character or any combined alphanumeric character. blank = match with 3p contactor q = match with quantum series used function c03 = for xmc0 3p series definite purpose contactors. accessory category j = mechanically interlocked block option note : spdt = single pole double throw, spst = single pole single throw, nc = normally closed, no = normally opened. 0 = match with 25-40a 1 = match with 50-63a type model nomenclature - ordering information 0 = none 3 = 1 spst-nc 1 = 1 spdt 4 = 1 spst-no option contact type c03 a = auxiliary contacts block accessory category m = microswitch block contact type 0 = none 3 = 1 spst-nc 1 = 1 spdt 4 = 1 spst-no c03 basic designation interlock type customer assigned suffix "x" where "x" may be any alphanumeric character or any combined alphanumeric character. position 1 position 2
- 4 - pole characteristics maximum horsepower(hp) full load amps(fla) poles voltage locked rotor amps (lra) resistive amps rating (res) voltage single phase three phase catalog number 25 1 240/277 480 600 150 - - 35 240/277 2 - xmc0-257* xmc0-251* 32 1 240/277 480 600 180 150 120 40 240/277 2 - xmc0-327* xmc0-321* 40 1 240/277 480 600 240 - - 50 240/277 3 - xmc0-407* xmc0-401 25 2 240/277 480 600 150 125 100 35 240/277 3 - xmc0-252* 32 2 240/277 480 600 180 150 120 40 240/277 3 - xmc0-322* 40 2 240/277 480 600 240 200 160 50 240/277 3 - xmc0-402* 25 2 3 240/277 480 600 150 125 100 35 240/277 480 600 3 - - 5 7.5 10 xmc0-253a* xmc0-253* 32 2 3 240/277 480 600 180 150 120 40 240/277 480 600 3 - - 7.5 10 15 xmc0-323a* xmc0-323* 40 2 3 240/277 480 600 240 200 160 50 240/277 480 600 5 - - 10 15 20 xmc0-403a* xmc0-403* 50 2 3 240/277 480 600 300 250 200+ 63 240/277 480 600 5 - - 15 20 25 xmc0-503a* xmc0-503* 63 2 3 240/277 480 600 360 300 240+ 75 240/277 480 600 7.5 - - 20 25 30 xmc0-633a* xmc0-633* 50 2 3 240/277 480 600 300 250 200 63 240/277 480 600 5 - - 15 20 25 xmc0-503a*z xmc0-503*z 63 2 3 240/277 480 600 360 300 240 75 240/277 480 600 7.5 - - 20 25 30 xmc0-633a*z xmc0-633*z 75 2 3 240/277 480 600 450 375 300 94 240/277 480 600 15 - - 25 40 40 xmc0-753a* xmc0-753* 90 2 3 240/277 480 600 540 450 360 120 240/277 480 600 15 - - 30 50 50 xmc0-903a* xmc0-903* notes: 1. all the models also could be marked or used for the actual ap plications which have less contact ratings than the certificate d ratings. the rating can be voltage, fla, lra or res. 2. all the ratings have not ?break all lines? restriction, ex cept the rating ?600vac 50fla/200lra? for ?xmc0-50 without z? and ?600vac 63fla/240lra? for ?xmc0-63 without z?. 3. contact factory representative for cd free option.
- 5 - auxiliary contacts block characteristics voltage rating 120vac 240vac 480vac 600vac amperes - break 3.0 1.5 0.75 0.6 amperes - make 30 15 7.5 6 contact rating - single circuit no or nc and two circuit no/nc amperes - thermal continuous 10 10 10 10 microswitch blocks characteristics contact rating - spdt 10a or 11a, 1/3 hp, 125 or 250 vac 1/2a, 125 vdc; 1/4a, 250 vdc 4a 120 vac on lamp load note: please contact us if you have any other request. coil characteristics @ 25 (cold state) part number max. inrushed va max. sealed va sealed watts voltage 60hz 50hz 60hz 50hz 60hz pick-up drop-out xmc0- 1/7 40 55 7.5 10 3 xmc0- 2 45 55 8 10.5 3.5 xmc0- 3/3a 80 90 12 16 5 xmc0-503/633 145 160 17.6 23 7 xmc0-753/903 300 325 35 46 12 0.8us 0.2us notes: 1. us=24vac 50/60hz(?e?coil) or 120vac 50/60hz(?f?coil) or 220vac/50hz, 240vac/60hz(?i?coil) or 277vac/60hz(?l? coil) or 415vac/50hz, 480vac/60hz(?n?coil). 2. inrushed va and sealed va test at us.
- 6 - outline dimensions 1 pole (metal plate, 25-40fla, w/o coil cover) 1 pole (metal base, 25-40fla, with coil cover)
- 7 - 1 pole+shunt (metal base, 25-40fla, w/o coil cover) 1 pole+shunt (metal base, 25-40fla, with coil cover)
- 8 - 2 pole (metal base, 25-40fla, w/o coil cover) 2 pole (metal base, 25-40fla, with coil cover)
- 9 - 3 pole (metal base, 25-40fla) - quantum series 3 pole (metal base, 25-40fla) 
- 10 - 3 pole (metal base, 50-63fla) - quantum series 3 pole (metal base, 50-63fla) 
- 11 -  3 pole (metal base, 75-90fla) auxiliary contact blocks - used for quantum series auxiliary contact blocks microswitch blocks - used for quantum series microswitch blocks interlock blocks - used for quantum series interlock blocks
- 12 - wiring diagram contactors: xmc0- 7 xmc0- 1 xmc0- 2 xmc0- 3 auxiliary contact blocks: 1nc 1no 1nc + 1no 2nc 2no remarks: 1) torque for screws 25 lb-in /lugs 25 lb-in for 25-40fla types; torque for screws 45 lb-in /lugs 50 lb-in for 50-63fla types; torque for screws 50 lb-in /lugs 60 lb-in for 75-90fla types; torque for screws 8 lb-in for auxiliary contact blocks; torque for coil screws 8 lb-in for 3-pole 25-40fla types and 12 lb-in for 50-90fla types. 2) for qc wiring, the female connector should meet iec 60760, necessary to ensure the reliability of connection between female connectors and qc terminals. 3) if the actual condition differs from this specif ication, please contact us for further discussion.


▲Up To Search▲   

 
Price & Availability of XMC0-503633

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X